Overview: The TTU301 is installed in the station area of pole mounted transformer, which has th···
Overview:
The TTU301 is installed in the station area of pole mounted transformer, which has the functions of power distribution, energy metering, reactive power compensation, three-phase load unbalance management, and the automatic measurement, acquisition, protection, monitoring, safety protection, etc. of power supply and consumption information for 0.4kV low voltage equipment of distribution transformer.
Features:
l Distribution transformer monitoring: Real-time collection and uploading of voltage, current, temperature and humidity data in the station area
l Automatic meter reading: Data collection of total meter in station area, to obtain the refined operation data of station area, the extendable broadband carrier reads the user’s meter data.
l Equipment monitoring: Automatic monitoring of equipment such as feeder switches and leakage switches in the station area.
l Intelligent reactive power compensation monitoring: Real-time data collection of intelligent reactive power compensation equipment.
l Micro-power wireless maintenance: Due to the complex environment of the installation location of the box, the terminal provides convenient on-site wireless debugging and upgrade.
l Three-phase unbalance management: Perform balance adjustment using commutation device according to the monitoring of three-phase unbalance situation in the station area.
l Fault location and indication: In-situ indication and automatic report by monitoring information such as its own status, external switch faults, etc.
l Safety protection: Information safety protection based on embedded security chip.
Technical Parameters:
 
 
 
 Power supply 
 
  | 
 Rated voltage 
  | 
 AC220V/380V, 50Hz  | 
 Allowable deviation 
  | 
 -30%~+30% 
  | |
 Rated current 
  | 
 5A  | |
 Precise measurement range 
  | Voltage  | 176-264V  | 
Current  | 0-6A  | |
Frequency  | 45Hz-55Hz  | |
 
 
 
 
 
 
 
 Measurement accuracy 
  | Voltage  | ≤±0.5%  | 
Current  | ≤±0.5%  | |
Frequency  | ≤0.01Hz  | |
Active power 
  | ≤±1%  | |
Reactive power 
  | ≤±1%  | |
Power factor 
  | ≤±1%  | |
inspecting power 
  | ≤±1.0%  | |
Electrical measurement 
  | ≤1.0%  | |
Terminal static power consumption 
  | ≤10 VA  | |
 Power consumption 
  | Voltage current Loop power consumption 
  | ≤0.5VA 
  | 
Backup power 
  | Super capacitor 
  | |
Communication channel 
  | RS485, 4G mobile, micro power wireless, Ethernet, carrier interface, USB           | |
      
 